3151AP absolute pressure transmitter adopts advanced-technology high-accurate compact smart sensor, to compensate temperature and static pressure with digital compensation technology which improves measuring accuracy and decreases temperature drift. With
Features
Microprocessor makes it more flexible and powerful;
With strong self-diagnose performance, zero and range regulation don’t influence each other;
With perfect remote and local set and calibration functions;
Two-wire system which is in accordance with HART PROTOCOL, can communicate with HART PROTOCOL terminal without interrupting output;
Digital compensation which can compensate to temperature and static pressure;
With good stability performance and high-accuracy, damping is adjustable, strong one-way overload resistant capacity;
Without mechanical driving components which reduce maintenance, solid and vibration-resistant;
Components are in common use which is easy for maintenance;
Wetted parts diaphragm material is optional and can be used for a day long.
Technical Parameters
Output signal: 4~20mAoutput with HART® protocol digital signal(two-wire system)
Power supply: Outside power24V DC, (power range 12V~45V)
Installation: Explosion-proof dⅡCT5, intrinsic safety iaⅡCT5
Drift features: Range upper and lower limit shall not exceed range limit after positive and negative drift. Maximum positive drift is 0.975URL, maximum negative drift is-URL at minimum range.
Temperature range: medium temperature -40~104℃, storage temperature -40~85℃, working temperature -40~85℃/-20~70℃ (with digital head)
Relative humidity: 0~100%
Damping: time constant within 0.2~32.0S is adjustable
Start time: 3S, no need to preheat
Performance: under standard test conditions like without drift, 316stainless steel isolation diaphragm etc.
Range ratio: 40:1
Accuracy: range is 3, 4, 5
Range ratio is 1:1 to 10:1, ±0.1% of calibration range
Range ratio is 10:1 to 40:1, ±0.05(1+0.1URL/range)% of range
Range is 6, 7, 8, 9, 0
Range ratio is 1:1 to 10:1, ±0.15% of calibration range
Range ratio is 10:1 to 40:1, ±0.075(1+0.1URL/range)% of range
Stability: error in six months is ±0.15% of maximum range
Over pressure influence: error in six months is ±0.15% of maximum range after being added 140kgf/cm²
Power supply influence: less than 0.005%/V of output range
Vibration influence: frequency is 200Hz at any axial direction; error is ±0.05%/g of maximum range
Load influence: provided voltage input transmitter is higher than 12V, there will be no load influence within load working area
Mounting influence: maximum zero error is more than 0.25 kPa, but adjustable without influence to range, when you measure body, there will be no influence to flange rotary.
Model
3151AP | Intelligent Absolute Pressure Transmitter | |||||||||||
| code | Gauge pressure range(KPa) | Absolute pressure range(KPa) | |||||||||
1 | 0-0.15~7.5 | 0-0.15~7.5 | ||||||||||
2 | 0-4~40 | 0-4~40 | ||||||||||
3 | 0-2~200 | 0-2~200 | ||||||||||
4 | 0-7~700 | 0-7~700 | ||||||||||
5 | 0-21~2100 | 0-21~2100 | ||||||||||
6 | 0-70~7000 | 0-70~7000 | ||||||||||
7 | 0-210~21000 | 0-210~21000(special range is customized) | ||||||||||
8 | 0-420~41000(special range is customized) |
| ||||||||||
| code | Output | ||||||||||
A | 4-20mA standard output | |||||||||||
H | 4-20mA+HARTprotocol | |||||||||||
F | FF bus protocol | |||||||||||
| code | Flange joint | Vent valve | Isolation diaphragm | Filling | |||||||
22 | 316SS | 316SS | 316SS | Silicon oil (normal) | ||||||||
23 | 316SS | 316SS | Hastelloy C | |||||||||
24 | 316SS | 316SS | Monel | |||||||||
25 | 316SS | 316SS | Tantalum | |||||||||
33 | Hastelloy C | Hastelloy C | Hastelloy C | |||||||||
35 | Hastelloy C | Hastelloy C | Tantalum | |||||||||
44 | Monel | Monel | Monel | |||||||||
| code | Connection | ||||||||||
O | 1/4NPT F | |||||||||||
T | 1/2NPT F | |||||||||||
S1 | With one remote device(positive pressure side) | |||||||||||
| code | Display | ||||||||||
D | Digital head | |||||||||||
M | Digital head with set button | |||||||||||
N | Without head | |||||||||||
| code | Mounting bracket | ||||||||||
B1 | Bend bracket pipe mounting 2" | |||||||||||
B2 | Bend bracket plate mounting | |||||||||||
B3 | Flat bracket pipe mounting 2" | |||||||||||
| code | Explosion performance | ||||||||||
Ex | Explosion-proof | |||||||||||
id | Intrinsic-safety | |||||||||||
3151AP | □ | □ | □ | □ | □ | □ | □ |
|