3151DR micro differential pressure transmitter adopts advanced-technology high-accurate compact smart sensor, to compensate temperature and static pressure with digital compensation technology which improves measuring accuracy and decreases temperature dr
Technical Parameters
Output signal: 4~20mAoutput with HART® protocol digital signal(two-wire system)
Power supply: Outside power24V DC, (power range 12V~45V)
Installation: Explosion-proof dⅡCT5, intrinsic safety iaⅡCT5
Drift features: Range upper and lower limit shall not exceed range limit after positive and negative drift. Maximum positive drift is 0.975URL, maximum negative drift is-URL at minimum range.
Temperature range: medium temperature -40~104℃, storage temperature -40~85℃, working temperature -40~85℃/-20~70℃ (with digital head)
Relative humidity: 0~100%
Damping: time constant within 0.2~32.0S is adjustable
Start time: 3S, no need to preheat
Performance: under standard test conditions like without drift, 316stainless steel isolation diaphragm etc.
Range ratio: 40:1
Static pressure and overpressure limit:
input pressure of 0~13.8MPa (absolute pressure) to any side of transmitter, it will not be broken;
transmitter can work under static pressure between 3.45kPa (absolute pressure) ~13.8MPa(gauge pressure)
flange pressure: 68.9MPa
Model
3151DR | Micro Differential Pressure Transmitter | ||||||||||
| code | Range(KPa) | |||||||||
1 | 0-0.1~1 | ||||||||||
| code | output | |||||||||
A | 4-20mA standard output | ||||||||||
H | 4-20mA+HART protocol | ||||||||||
F | FF bus protocol | ||||||||||
| code | Flange joint | Vent valve | Isolation diaphragm | Filling | ||||||
22 | 316SS | 316SS | 316SS | Silicon oil (normal) | |||||||
23 | 316SS | 316SS | Hastelloy C | ||||||||
24 | 316SS | 316SS | Monel | ||||||||
25 | 316SS | 316SS | Tantalum | ||||||||
33 | Hastelloy C | Hastelloy C | Hastelloy C | ||||||||
35 | Hastelloy C | Hastelloy C | Tantalum | ||||||||
44 | Monel | Monel | Monel | ||||||||
| code | Connection | |||||||||
O | 1/4NPT F | ||||||||||
T | 1/2NPT F | ||||||||||
S1 | With one remote device(positive pressure side) | ||||||||||
S2 | With two remote devices | ||||||||||
| code | Display | |||||||||
D | Digital head | ||||||||||
M | Digital head with set button | ||||||||||
N | Without head | ||||||||||
| code | Mounting bracket | |||||||||
B1 | Bend bracket pipe mounting 2" | ||||||||||
B2 | Bend bracket plate mounting | ||||||||||
B3 | Flat bracket pipe mounting 2" | ||||||||||
| code | Explosion performance | |||||||||
Ex | Explosion-proof | ||||||||||
id | Intrinsic-safety | ||||||||||
3151DR | □ | □ | □ | □ | □ | □ | □ |
|